Skip to Main Content
Let's Talk
Menu Close
University of Texas Austin Chilled Water Energy Optimization | Optimum Energy Case Study
Case Study
Higher Education · Chilled Water Optimization

University of Texas Austin Chilled Water Plant Optimization

Enduring partnership delivers innovation, efficiency and energy savings

LocationAustin, TX
IndustryHigher Education
Years with Optimum15+
25%
Plant Efficiency Improvement
29.2M kWh
Annual Energy Savings
72,000 Tons
CO₂ Prevented Per Year
4.2 MW
Peak Load Reduction
Overview

Reducing Energy Usage While Growing the Campus

To meet campus growth needs, the University of Texas at Austin found it far more economical to be more efficient than to invest in new power production capacity. Working in partnership with Optimum Energy, UT achieved what seemed impossible: reducing the chilled water system’s overall energy usage even as the campus grew.

Improving plant efficiency began in 2007, when Juan Ontiveros, UT’s associate vice president for Utilities and Energy Management, began working with Optimum Energy to optimize the school’s only all-variable-speed, 15,000-ton, 3-chiller plant (Chilling Station 6; CS6), using OptimumLOOP® and the OptiCx® platform.

OptimumLOOP® uses patented power-based relational controls to dynamically adjust flows and condenser water temperatures in the cooling towers. By lowering the lift on the chiller and reducing the chiller speed, the solution brought the cooling cost as low as 0.3 kW/ton in the winter—delivering what Ontiveros called “a free cooling effect—with chillers.”

Efficiency Over Time

Annual Average kW/ton: 2006–2024

Campus efficiency improved steadily from 0.79 kW/ton in 2006 to 0.59 kW/ton by 2024—all while adding 3.5 million square feet of buildings.

Annual Average kW/ton
The Challenge

Gaining Efficiency from an Already Efficient System

With CS6 already optimized, the team tackled three interconnected challenges to push efficiency even further.

Hydraulic Constraints

Physical hydraulic constraints were affecting flow in the campus chilled-water distribution loop. A real-time hydraulic flow model revealed the system was over-pressurized, creating false building loads.

Over-Pressurized System

Pumping too much water created false building loads, forcing excess steam production. Reducing to 8 psi at peak and 2 psi in winter cut 1,500 hp of pumping energy.

Static Chilled Water Temperature

Chilled water had been set at 39°F year-round. OptiCx® visibility enabled dynamic adjustment up to 44°F based on real-time conditions, significantly cutting chiller load.

Going the Last Mile

Predictive Thermal Energy Dispatch

Thanks to their long partnership, Optimum and UT engineers could think differently about how to boost efficiency of a system already operating at peak performance. The question: could Optimum develop a solution using power generation data and weather forecasts to predict and dynamically handle cooling while optimizing thermal energy storage?

Optimum first captured historical plant and weather data going back 3 years. Using OptiCx®, the team built an automated control strategy that uses weather forecast information to determine power requirements for the entire campus 48 hours in the future.

The result was dramatic: differential loads dropped from 20 MW to just 4–5 MW. OptiCx® now raises the cooling load at night—running the most efficient chillers to charge the tanks—and during the day discharges the stored chilled water while keeping backup machines on standby.

Total annual power plant operating efficiency reached 88.59%. Since 2008, chilled water production’s overall energy use has remained flat despite adding 3.5 million square feet of buildings.

Results

Savings That Defy Expectations

Compared to the baseline year of 2008, the results speak for themselves.

29.2M kWh

Annual Electrical Energy Savings

Compared to 2008 baseline levels, saved year over year

72,000 Tons

Annual CO₂ Emissions Reduction

Equivalent to taking tens of thousands of cars off the road every year

4.2 MW

Peak Load Reduction

Electrical demand reduction vs. 2008 baseline

0.59 kW/ton

Post-Optimization Efficiency

Down from 0.79 kW/ton — a 25% plant efficiency improvement

3.5 M

Square Feet Added

Campus grew significantly (2009–2019) while energy use stayed flat

88.59%

Power Plant Operating Efficiency

Total annual power plant efficiency achieved

Project Benefits

Beyond Energy: Operational Gains

Energy savings
Reduced electrical demand
Reduced water consumption & treatment costs
Cost savings
CO₂ emissions reduction
Improved equipment life
Improved resilience
Time savings for equipment maintenance
Reduced plant operator stress
The secret to our success is having the right balance of plant equipment, marrying that with the optimization and dispatching opportunities Optimum provides, and doing it in a way they don’t compromise or fight each other. When they do good, we do good.
— Juan Ontiveros, Associate Vice President for Utilities & Energy Management, UT Austin
Bottom Line

The Same Energy. A Much Bigger Campus.

“We’re now using the same amount of energy we did before we added CS7,” says Ontiveros. “And we reduced our fuel use. You’re not supposed to be able to do that.”

The UT Austin partnership demonstrates what’s possible when a university commits to a long-term, data-driven optimization strategy. By continuously pushing the boundaries of what’s achievable—from basic chiller optimization to predictive thermal dispatch—Optimum Energy and UT Austin have set a new benchmark for higher education energy efficiency.

“I think we both have learned a lot,” says Ontiveros. “Together, we take a very methodical approach. And Optimum also forced us to become almost religious about accurate data.”